High voltage/low voltage prefabricated substation
High voltage/low voltage prefabricated substation
Technical parameters of YB ‑12 high‑voltage/low‑voltage prefabricated substation
| Name | Unit | High voltage electrical equipment | transformer | Low voltage electrical equipment |
|---|---|---|---|---|
| Rated Voltage | kV | 10 | 10/10.4 | 0.4 |
| Rated Current | A | 630 | 100~2500 | |
| rated frequency | Hz | 50 | 50 | 50 |
| Rated capacity | kVA | 100‑1250 | ||
| Rated thermal stability current | kA | 20/4S | 30/1S | |
| Rated dynamic stability current (peak value) | kA | 50 | 63 | |
| Rated closing short‑circuit current (peak value) | kA | 50 | 15~30 | |
| Rated breaking short‑circuit current | kA | 31.5 (Fuse) | ||
| Rated breaking load current | A | 630 | ||
| 1‑minute power frequency withstand voltage | kV | To the ground, alternating 42 48 between fracture surfaces | 35/28(5min) | 20/2.5 |
| Lightning impulse withstand voltage | kV | To the ground, 75 between phases, 85 between fractures | 75 | |
| Shell protection level | dB | IP23 | IP23 | IP23 |
| noise level | 个 | Oil change ≤ 55 Dry change ≤ 65 | ||
| Number of circuits | kvar | 1~6 | 2 | 4~30 |
| Maximum reactive power compensation on the low voltage side | 300 |